4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCM
1162 List Manual (LH8), 02/2015, 6RX1800-0ED76
100: Bootloader version not compatible.
101: TMS version not compatible.
Note:
r50047[1]: Error bits. Indicate in which of the following states errors occurred.
Bit 0 = 1: Initialization
Bit 1 = 1: TMS320 status
Bit 2 = 1: Bootloader version
Bit 3 = 1: TMS320 version
Bit 4 = 1: TMS320 start
Bit 5 = 1: Load Flash interface
Bit 6 = 1: Delete Flash
Bit 7 = 1: Write Flash
Bit 8 = 1: Request code
Bit 9 = 1: TMS320 start
Bit 10 = 1: Read message
Remedy: Carry out a POWER ON (power off/on) for all components.
Reaction upon N: NONE
Acknowl. upon N: NONE
Reaction upon A: NONE
Acknowl. upon A: NONE
F60066 (N, A) Error communicating with sensors
Message value: %1
Message class: Internal (DRIVE-CLiQ) communication error (12)
Drive object: DC_CTRL
Reaction: OFF2 (NONE, OFF1, OFF3)
Acknowledge: IMMEDIATELY
Cause: An error occurred when polling the fan speeds and temperature sensors.
Fault value (r0949, interpret decimal):
1: Data not received
2: Fan monitoring or temperature sensors not switched over
Remedy: Carry out a POWER ON (power off/on) for all components.
Reaction upon N: NONE
Acknowl. upon N: NONE
Reaction upon A: NONE
Acknowl. upon A: NONE
F60067 (N, A) Fault temperature too high
Message value: %1
Message class: Overtemperature of the electronic components (6)
Drive object: DC_CTRL
Reaction: OFF2 (NONE, OFF1, OFF3)
Acknowledge: IMMEDIATELY
Cause: The temperature at one of the temperature sensors has exceeded the highest permissible temperature to initiate this
fault.
Fault value (r0949, interpret decimal):
1: Overtemperature at sensor 1 (sensor an XT5).
2: Overtemperature at sensor 2 (sensor an XT6).
3: Overtemperature at sensor 3 (sensor an XT7).
4: Overtemperature at the sensor control module (A7105, A7106, A7107, A7108, A7109).
Note:
r50047[1]: Temperature sensor 1
r50047[2]: Temperature sensor 2
r50047[3]: Temperature sensor 3