SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
529
2 Parameters
2.2 List of parameters
Description: Setting to reset the operating hours of the device fan that have accumulated.
Value: 0: Inactive
1: Reset
Index: [0] = Fan terminal XV1
[1] = Fan terminal XV2
[2] = Fan terminal XV3
[3] = Fan terminal XV4
[4] = Fan ON
Dependency: Refer to: r50960, p50961
Note: Procedure to reset the operating hours:
Set p50962[x] = 1
The parameter is automatically set to zero after this is done.
Description: Behavior of the fan control:
0 : The fan control takes into account the temperature sensor.
1 : The fan control does not take into account the temperature sensor.
Value: 0: The fan control takes into account the temperature sensor.
1: The fan control doesn't take into account the temperature sensor
Dependency: Refer to: r50960, p50961
Note: Setting 1:
The fan is only switched off after the parameterized fan run-on time, independent of the various temperature
measurements and independent of the calculated thyristor temperature rise (=barrier layer temperature of the
thyristors).
As a consequence, it is also possible to acknowledge a fan fault even at ambient temperatures > 35°.
Description: Sets the signal sources for the binector inputs on the binector-connector converter.
Dependency: Refer to: r52620
p50962[0...4] Device fan reset operating hours / Dev_fan reset h
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: - Func. diagram: 8045
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
p50963 Behavior of the fan control / Behavior fan ctrl
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: - Func. diagram: 8047
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
p51117[0...15] BI: Binector-connector converter signal source / Bin/con sig s
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 9300
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0