2 Parameters
2.2 List of parameters
SINAMICS DCM
72 List Manual (LH8), 02/2015, 6RX1800-0ED76
Notice: This parameter is automatically pre-set for encoders from the encoder list (p0400). When selecting a catalog
encoder, this parameter cannot be changed (write protection). Information in p0400 should be carefully observed
when removing write protection.
Description: Sets the configuration for an SSI encoder.
Notice: This parameter is automatically pre-set for encoders from the encoder list (p0400).
When selecting a catalog encoder, this parameter cannot be changed (write protection). Information in p0400 should
be carefully observed when removing write protection.
Note: Re bit 06:
The quiescent signal level of the data line corresponds to the inverted, set level.
Description: Sets the configuration of the Sensor Module.
Notice: A bit-wise configuration is only possible if the corresponding property is also present in r0458.
Note: Re bit 17 (burst oversampling):
- if bit = 1, burst oversampling is switched on.
Re bit 18 (continuous oversampling):
- if bit = 1, continuous oversampling is switched on.
Re bit 19 (Safety position actual value sensing):
- if bit = 1, the Safety position actual value is transferred in the cyclic telegram.
Re bit 20 (speed calculation mode):
- if bit = 1, the speed is calculated via incremental difference without extrapolation.
- if bit = 0, the speed is calculated via edge time measurement with extrapolation. p0453 is effective in this mode.
p0429[0...n] Encoder SSI configuration / Enc SSI config
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed: C2(4) Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: EDS, p0140 Func. diagram: -
P-Group: Encoder Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Transfer code Binary code Gray code -
02 Transfer absolute value twice Yes No -
06 Data line during the monoflop time High level Low level -
p0430[0...n] Sensor Module configuration / SM config
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed: C2(4) Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: EDS, p0140 Func. diagram: -
P-Group: Encoder Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 1110 0000 0000 1000 0000
0000 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
17 Burst oversampling Yes No -
18 Continuous oversampling (reserved) Yes No -
19 Safety position actual value sensing Yes No -
20 Speed calculation mode (only SMC30) Incremental diff Flank time meas -
21 Zero mark tolerance Yes No -
22 Rot pos adapt Yes No -
23 De-select commutation with zero mark Yes No -
24 Commutation with selected zero mark Yes No -
25 Switch off encoder voltage supply during
parking
Yes No -
27 Extrapolate position values Yes No -
28 Cubic correction Yes No -
29 Phase correction Yes No -
30 Amplitude correction Yes No -
31 Offset correction Yes No -