SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
427
2 Parameters
2.2 List of parameters
Description: Sets the damping of a PT2 element for the reference model of the speed controller.
Recommendation: The reference model is correctly set when the characteristics of r52154 (reference model output) and r52167 (actual
speed value) are virtually identical when the I component of the speed controller is disabled.
Dependency: In conjunction with p50237 and p50239, the characteristics (in time) of the P-controlled speed control loop can be
emulated.
Refer to: p50237, p50239
Description: Sets the "fractional" dead time for the reference model of the speed controller.
This parameter emulates the computing dead time of the proportionally controlled speed control loop.
The multiplier set refers to the speed controller clock cycle.
Recommendation: The reference model is correctly set when the characteristics of r52154 (reference model output) and r52167 (actual
speed value) are virtually identical when the I component of the speed controller is disabled.
Dependency: In conjunction with p50237 and p50238, the characteristics (in time) of the P-controlled speed control loop can be
emulated.
Refer to: p50237, p50238
Description: Setting to activate the influence of the reference model for the speed controller.
Value: 0: Reference model not effective
1: Reference model effective
Dependency: Refer to: p50241
Description: Sets the signal source for the input signal of the reference model for the speed controller.
Dependency: Refer to: p50240
p50238[0...n] Speed controller reference model damping / n_ctrl ref_m d
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6812
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.000 5.000 1.000
p50239[0...n] Speed controller reference model dead time / n_ctr ref_m t_dead
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6812
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 2.00 0.00
p50240[0...n] Speed controller reference model activation / n_ctrl ref_m act
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: DDS, p0180 Func. diagram: 6815
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
p50241 CI: Speed controller reference model signal source / n_ctrl ref_m sig s
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: Unsigned32 / FloatingPoint32 Dyn. index: - Func. diagram: 6815
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- - 52155[0]

Table of Contents

Other manuals for Siemens SINAMICS DCM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS DCM and is the answer not in the manual?

Siemens SINAMICS DCM Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS DCM
CategoryMedia Converter
LanguageEnglish

Related product manuals