2 Parameters
2.2 List of parameters
SINAMICS DCM
368 List Manual (LH8), 02/2015, 6RX1800-0ED76
Description: Sets the component, whose feeder cable is monitored for data transfer errors.
The feeder cable is the DRIVE-CLiQ cable that is connected to a component in the direction of the Control Unit.
Errors that have occurred in the selected time interval (p9939) can be read-out from r9943.
Dependency: Refer to: r9936, p9938, p9939, r9943
Description: Displays the connection errors of the individual connection that have occurred within the time interval (p9939).
The detailed diagnostics for the individual connection is activated via p9938 > 0 and is selected via p9942.
Dependency: Refer to: r9936, p9938, p9939, p9942
Description: Displays the measured system utilization.
The higher the value displayed, the higher the system utilization.
Index: [0] = Computing time utilization (min)
[1] = Computing time utilization (averaged)
[2] = Computing time utilization (max)
[3] = Largest total utilization (min)
[4] = Largest total utilization (averaged)
[5] = Largest total utilization (max)
[6] = Reserved
[7] = Reserved
Dependency: Refer to: r9976, r9979, r9980, r9981
Note: Re index 3 ... 5:
The total utilizations are determined using all sampling times used. The largest total utilizations are mapped here.
The sampling time with the largest total utilization is displayed in r9979.
Total utilization:
Computing time load of sampling time involved including load from higher-priority sampling times (interrupts).
p9942 DRIVE-CLiQ detailed diagnostics select individual connection / DQ detail conn
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: U, T Calculated: - Access level: 4
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 199 0
r9943 DRIVE-CLiQ detailed diagn. individual connection error counter / DQ det err counter
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: - Calculated: - Access level: 4
Data type: Integer32 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
r9975[0...7] System utilization measured / Sys util meas
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: - Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]