441
2 Parameters
2.2 List of parameters
Description: Sets the enable for ramp-function generator tracking.
Value: 0: Inhibit
1: Enable
Dependency: RFG tracking has to be controlled by setting a 1 signal at binector input p50647.
Refer to: p50647
Description: Selection of the setting value for the ramp-function generator output for OFF1.
Value: 0: Ramp-function generator output not set
1: Set RFG output to setting value 1
2: Set RFG output to setting value 2
Recommendation: During "shutdown", limiting is not applied to the ramp-function generator output. As limiting the ramp-function
generator output during "shutdown" does not generate a temporary increase in speed, p50318 should be set to 1 or
2.
Dependency: Refer to: p50650
Note: If p50318 = 0:
The ramp-function generator output is not set.
If p50318 = 1:
The value supplied via connector input p50650[0] is applied as the setting value.
If p50318 = 2:
The value supplied via connector input p50650[1] is applied as the setting value.
Description: Sets the delay time for enabling the setpoint on the ramp-function generator.
In the case of a setpoint enable, the setpoint is not injected on the ramp-function generator until this time has
elapsed.
Bit field: Bit Signal name 1 signal 0 signal FP
00 RFG enable ON OFF 3152
01 RFG start ON OFF 3152
02 Setpoint enable & OFF1 ON OFF 3152
03 Set ramp-function generator ON OFF 3152
04 Track ramp-function generator ON OFF 3152
05 Bypass ramp-function generator ON OFF 3152
07 Ramp-down ON OFF 3152
15 Ramp-up ON OFF 3152
p50317[0...n] RFG tracking enable / RFG track ena
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: DDS, p0180 Func. diagram: 3152
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
p50318[0...n] RFG setting value selection / RFG set val sel
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: DDS, p0180 Func. diagram: 3152
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 2 0
p50319[0...n] RFG setpoint enable delay time / RFG set_ena i_del
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 3151
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [s] 10.00 [s] 0.00 [s]