SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
357
2 Parameters
2.2 List of parameters
Note: All indices of r9491 to p9493 designate the same interconnection.
r9491[x] contains the signal receiver and r9492[x] the matching signal source; p9493[x] can be set to modify the
interconnection.
Description: Setting to reset the BICO interconnections to other drives.
Each interconnection can be individually reset.
Value: 0: Set connection to 0
1: Set connection to 1 (100 %)
2: Set connection to factory setting
15: Finished
Dependency: Refer to: r9490, r9491, r9492
Note: All indices of r9491 to p9493 designate the same interconnection.
r9491[x] contains the signal receiver and r9492[x] the matching signal source; p9493[x] can be set to modify the
interconnection.
Description: Sets the behavior for BICO interconnections to drive objects that are either not capable of operation or have been
deactivated.
BO/CO parameters are on the drive object that is either not capable of operation or has been deactivated (signal
source).
Value: 0: Inactive
1: Save interconnections
2: Save interconnections and establish the factory setting
Dependency: Refer to: p9496, p9497, p9498, p9499
Note: For p9495 = 0, the following applies:
- the number of interconnections is zero (p9497 = 0).
For p9495 not equal to 0, the following applies:
- the BI/CI parameters involved are listed in p9498[0...29] (signal sink).
- the associated BO/CO parameters are listed in p9499[0...29] (signal source).
Description: Sets the behavior when activating BICO interconnections to drive objects that are either not capable of operation or
have been deactivated.
Value: 0: Inactive
1: Restore the interconnections from the list
2: Delete the interconnections from the list
p9493[0...9] Reset BICO interconnections to other drives / Reset BICO to drv
All objects Can be changed: T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 15 15
p9495 BICO behavior for de-activated drive objects / Behav for deact DO
All objects Can be changed: T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 2 0
p9496 BICO behavior when activating drive objects / Behav when act DO
All objects Can be changed: T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 2 0