2 Parameters
2.2 List of parameters
SINAMICS DCM
458 List Manual (LH8), 02/2015, 6RX1800-0ED76
Description: Sets the signal source for the selection of the connectors (p50431[0 to 7]).
Dependency: Refer to: p50431, p50432, p50680, p50681, r52204, r52209, r52210, r53170
Description: Sets the signal sources for generating the fixed setpoint (CO: r52204).
Dependency: Refer to: p50430, p50432, p50680, p50681, r52204, r52209, r52210, r53170
Description: Setting to enable or disable the impact of the individual fixed setpoints when generating signal r53170.10, "Bypass
ramp-function generator".
Value: 0: Inhibit
1: Enable
Dependency: Refer to: r53170
Note: [0] = Enable bypassing of ramp-function generator at fixed setpoint 0
...
[7] = Enable bypassing of ramp-function generator at fixed setpoint 7
Description: Sets the signal source for the default setpoint.
p50430[0...7] BI: Fixed setpoint signal source for connector selection / Fix set conn sig s
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 3115
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p50431[0...7] CI: Signal source for fixed setpoint / Fix set sig s
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: Unsigned32 / FloatingPoint32 Dyn. index: - Func. diagram: 3115
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- - 0
p50432[0...7] Fixed setpoint bypass ramp-function generator / Fix set bypass RFG
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: - Func. diagram: 3115
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
p50433[0...n] CI: Signal source for default setpoint / Def set sig s
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: Unsigned32 / FloatingPoint32 Dyn. index: CDS, p0170 Func. diagram: 3113
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- - 52011[0]