SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
187
2 Parameters
2.2 List of parameters
Description: Displays the error (system deviation) between the setpoint and actual value of the technology controller.
Dependency: Refer to: p2263
Description: Sets the time constant for the differentiation (D component) of the technology controller.
Note: p2274 = 0: Differentiation is disabled.
Description: Sets the proportional gain (P component) of the technology controller.
Dependency: Refer to: p2252
Note: p2280 = 0: The proportional gain is disabled.
Description: Sets the integral time (I component, integrating time constant) of the technology controller.
Dependency: Refer to: p2252
Note: p2285 = 0: The integral time is disabled.
Description: Sets the signal source to hold the integrator for the technology controller.
r2273 CO: Technology controller error / Tec_ctrl error
DC_CTRL (Tech_ctrl),
DC_CTRL_R
(Tech_ctrl),
DC_CTRL_R_S
(Tech_ctrl),
DC_CTRL_S
(Tech_ctrl)
Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 7958
P-Group: Technology Unit group: 9_1 Unit selection: p0595
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
p2274 Technology controller differentiation time constant / Tec_ctrl D comp T
DC_CTRL (Tech_ctrl),
DC_CTRL_R
(Tech_ctrl),
DC_CTRL_R_S
(Tech_ctrl),
DC_CTRL_S
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 7958
P-Group: Technology Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.000 [s] 60.000 [s] 0.000 [s]
p2280 Technology controller proportional gain / Tec_ctrl Kp
DC_CTRL (Tech_ctrl),
DC_CTRL_R
(Tech_ctrl),
DC_CTRL_R_S
(Tech_ctrl),
DC_CTRL_S
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 7958
P-Group: Technology Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.000 1000.000 1.000
p2285 Technology controller integral time / Tec_ctrl Tn
DC_CTRL (Tech_ctrl),
DC_CTRL_R
(Tech_ctrl),
DC_CTRL_R_S
(Tech_ctrl),
DC_CTRL_S
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 7958
P-Group: Technology Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.000 [s] 60.000 [s] 0.000 [s]
p2286[0...n] BI: Hold technology controller integrator / Tec_ctr integ hold
DC_CTRL (Tech_ctrl),
DC_CTRL_R
(Tech_ctrl),
DC_CTRL_R_S
(Tech_ctrl),
DC_CTRL_S
(Tech_ctrl)
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: CDS, p0170 Func. diagram: 7958
P-Group: Technology Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0