4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCM
1166 List Manual (LH8), 02/2015, 6RX1800-0ED76
Remedy: Check the power supply.
Reaction upon N: NONE
Acknowl. upon N: NONE
Reaction upon A: NONE
Acknowl. upon A: NONE
F60092 (N, A) Reference voltage N10 outside tolerance
Message value: -
Message class: General drive fault (19)
Drive object: DC_CTRL
Reaction: OFF2 (NONE)
Acknowledge: IMMEDIATELY
Cause: The reference voltage N10 (-10 V) at terminal X177.32 lies outside the tolerance (deviation greater than +/-5%).
Note:
r50047[1]: Reference voltage -10 V (in volts)
r50047[2]: Reference voltage +10 V (in volts)
r50047[3]: Module temperature (in °C)
Remedy: Check the power supply.
Reaction upon N: NONE
Acknowl. upon N: NONE
Reaction upon A: NONE
Acknowl. upon A: NONE
F60093 (N, A) Power supply P5 overloaded
Message value: -
Message class: General drive fault (19)
Drive object: DC_CTRL
Reaction: OFF2 (NONE)
Acknowledge: IMMEDIATELY
Cause: Power supply P5 (+5 V) at connector X179.1 is overloaded.
Note:
r50047[1]: Reference voltage +10 V (in volts)
r50047[2]: Reference voltage -10 V (in volts)
r50047[3]: Module temperature (in °C)
Remedy: Identify the reason for the overload and rectify the situation.
Reaction upon N: NONE
Acknowl. upon N: NONE
Reaction upon A: NONE
Acknowl. upon A: NONE
F60094 (N, A) Power supply P15 overloaded
Message value: -
Message class: General drive fault (19)
Drive object: DC_CTRL
Reaction: OFF2 (NONE)
Acknowledge: IMMEDIATELY
Cause: Power supply P15 (+15 V) at terminal X177.41 is overloaded.
Note:
r50047[1]: Reference voltage +10 V (in volts)
r50047[2]: Reference voltage -10 V (in volts)
r50047[3]: Module temperature (in °C)
Remedy: Identify the reason for the overload and rectify the situation.
Reaction upon N: NONE
Acknowl. upon N: NONE