SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
367
2 Parameters
2.2 List of parameters
Description: Sets the configuration for the DRIVE-CLiQ detailed diagnostics (r9943).
Using the detailed diagnostics, it is possible to investigate data transfer errors on an individual connection, selected
using p9942.
Value: 0: Inactive
1: Sum send and receive errors
2: Only send errors
3: Only receive errors
4: Siemens internal
5: Siemens internal
6: Siemens internal
Dependency: The functions in p9938 can only be set for p9937.0 = 0.
Refer to: r9936, p9937, p9939, p9942
Notice: If value = 0:
- detailed diagnostics is inactive.
- the error counter is active (r9936).
If value > 0:
- the error counter is inactive (r9936).
- the detailed diagnostics as configured is active (r9943).
Description: Sets the time interval for recording the error counter in r9943.
Dependency: Refer to: r9936, p9938, p9942, r9943
Description: For p9941 =1, the serial numbers of all components in the target topology are deleted (zero is written).
Through activation and de-activation this enables the actual topology components to be newly assigned to the target
topology components.
Note: p9941 is automatically set to 0 at the end of the operation.
A warm restart is triggered automatically after p0009 = 0.
p9938 DRIVE-CLiQ detailed diagnostics configuration / DQ diag config
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: U, T Calculated: - Access level: 4
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 6 0
p9939 DRIVE-CLiQ detailed diagnostics time interval / DQ detail t_interv
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: U, T Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1 [s] 3600 [s] 1 [s]
p9941 Target topology feature delete all components / Feature delete
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: C1(1) Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Topology Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 0
Min Max Factory setting
0 1 0