SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
451
2 Parameters
2.2 List of parameters
Description: Sets the factor for the setpoint in the context of field current monitoring.
Dependency: Refer to: p50265, p50397
Refer to: F60005
Description: Sets the delay time for triggering fault F60005 in the context of field current monitoring.
Dependency: Refer to: p50265, p50396
Refer to: F60005
Description: Sets the factor for the setpoint for the "Field current actual value less than setpoint" message.
Dependency: Refer to: p50399, r53026
Note: This threshold also affects the phase logic execution in the context of the Direction reversal by field reversal and
Braking by field reversal functions.
The "Field current actual value less than setpoint" message is displayed via r53026.1.
Description: Sets the hysteresis for the "Field current actual value less than setpoint" message.
The message is triggered when the threshold is undershot (setpoint x factor).
Once the value rises above the threshold (setpoint x factor) plus the hysteresis, the message is withdrawn.
Dependency: Refer to: p50398, r53026
Note: The "Field current actual value less than setpoint" message is displayed via r53026.1.
p50396[0...n] Field current monitoring setpoint factor / If_mon set_fact
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 8044
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
1 [%] 100 [%] 50 [%]
p50397[0...n] Field current monitoring fault delay time / If_mon F t_del
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 8044
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.02 [s] 60.00 [s] 0.50 [s]
p50398[0...n] Messages for field current actual value less than setpoint fact / Msg If<set fact
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 8025
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
0.00 [%] 200.00 [%] 80.00 [%]
p50399[0...n] Messages for field current actual value less than setpoint hyst / Msg If<set hyst
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 8025
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
0.00 [%] 100.00 [%] 1.00 [%]