2 Parameters
2.2 List of parameters
SINAMICS DCM
212 List Manual (LH8), 02/2015, 6RX1800-0ED76
Description: Displays the actual value at the digital inputs.
This means that the actual input signal can be checked at terminal DI x or DI/DO x prior to switching from the
simulation mode (p4095.x = 1) to terminal mode (p4095.x = 0).
Note: If a DI/DO is parameterized as output (p4028.x = 1), then r4021.x = 0 is displayed.
DI: Digital Input
DI/DO: Bidirectional Digital Input/Output
Description: Displays the status of the digital inputs of Terminal Module 15 (TM15).
r4021 TM31 digital inputs terminal actual value / TM31 DI act value
TM31 Can be changed: - Calculated: - Access level: 2
Data type: Unsigned32 Dyn. index: - Func. diagram: 9549, 9550,
9552, 9560, 9562
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (X520.1) High Low -
01 DI 1 (X520.2) High Low -
02 DI 2 (X520.3) High Low -
03 DI 3 (X520.4) High Low -
04 DI 4 (X530.1) High Low -
05 DI 5 (X530.2) High Low -
06 DI 6 (X530.3) High Low -
07 DI 7 (X530.4) High Low -
08 DI/DO 8 (X541.2) High Low -
09 DI/DO 9 (X541.3) High Low -
10 DI/DO 10 (X541.4) High Low -
11 DI/DO 11 (X541.5) High Low -
r4022.0...23 CO/BO: TM15DI/DO digital inputs status / TM15D DI status
TM15DI_DO Can be changed: - Calculated: - Access level: 1
Data type: Unsigned32 Dyn. index: - Func. diagram: 9399, 9400,
9401, 9402
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI/DO 0 (X520.2) High Low -
01 DI/DO 1 (X520.3) High Low -
02 DI/DO 2 (X520.4) High Low -
03 DI/DO 3 (X520.5) High Low -
04 DI/DO 4 (X520.6) High Low -
05 DI/DO 5 (X520.7) High Low -
06 DI/DO 6 (X520.8) High Low -
07 DI/DO 7 (X520.9) High Low -
08 DI/DO 8 (X521.2) High Low -
09 DI/DO 9 (X521.3) High Low -
10 DI/DO 10 (X521.4) High Low -
11 DI/DO 11 (X521.5) High Low -
12 DI/DO 12 (X521.6) High Low -
13 DI/DO 13 (X521.7) High Low -
14 DI/DO 14 (X521.8) High Low -
15 DI/DO 15 (X521.9) High Low -
16 DI/DO 16 (X522.2) High Low -
17 DI/DO 17 (X522.3) High Low -
18 DI/DO 18 (X522.4) High Low -
19 DI/DO 19 (X522.5) High Low -