2 Parameters
2.2 List of parameters
SINAMICS DCM
542 List Manual (LH8), 02/2015, 6RX1800-0ED76
Note: Active faults are signaled at r2139.3 and r3114.10.
Description: Sets the signal source to select the required power unit topology.
Description: Sets the signal source for the feedback signal of the active power unit topology.
Description: Sets the stabilization time for the feedback signal of the active power unit topology.
Description: Sets the maximum duration of the power unit topology switchover.
Description: Sets the mode of operation of the armature converter for power unit topology 2.
Value: 0: Standard mode of operation
1: Sole power unit 1-phase
3: Sole power unit 3-phase
21: 12-pulse parallel, firing angle from the master
22: 12-pulse parallel, firing angle master/slave
31: 6-pulse serial, firing angle from the master
32: 6-pulse serial with sequential phase control
p51790 BI: Topology switchover signal source / Top_switch s_src
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 9360
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p51791 BI: Topology switchover feedback signal source / Top_sw fdbk s_src
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 9360
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p51792 Topology switchover feedback signal stabilization time / Topo_sw t_stab
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 9360
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 1000 [ms] 0 [ms]
p51793 Topology switchover feedback signal duration / Topo_sw fdbk t_sig
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 9360
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 10000 [ms] 100 [ms]
p51794 Topology switchover armature converter mode of operation 2 / Topo_sw mode 2
DC_CTRL Can be changed: T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: 9360
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 42 0