SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
279
2 Parameters
2.2 List of parameters
Description: Sets the pulse width for the signal to be generated for the function generator.
Dependency: Only effective when p4820 = 1 (square-wave).
Description: Sets the bandwidth for the signal to be generated for the function generator.
Dependency: Only effective when p4820 = 4 (PRBS).
Refer to: p4830
Description: Sets the amplitude for the signal to be generated for the function generator.
Dependency: Units are dependent on p4810.
If p4810 = 1, 2, 4: The amplitude is referred to p2002 (reference current).
If p4810 = 3, 5: The amplitude is referred to p2000 (reference speed).
Description: Sets the second amplitude for the signal to be generated for the function generator.
Dependency: Only effective for p4820 = 2 (staircase).
Units are dependent on p4810.
If p4810 = 1, 2, 4: The amplitude is referred to p2002 (reference current).
If p4810 = 3, 5: The amplitude is referred to p2000 (reference speed).
p4822 Function generator pulse width / FG pulse width
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Trace and function generator Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 0
Min Max Factory setting
0.00 [ms] 60000.00 [ms] 500.00 [ms]
p4823 Function generator bandwidth / FG bandwidth
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Trace and function generator Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 0
Min Max Factory setting
0.0025 [Hz] 16000.0000 [Hz] 4000.0000 [Hz]
p4824 Function generator amplitude / FG amplitude
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Trace and function generator Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 0
Min Max Factory setting
-1600.00 [%] 1600.00 [%] 5.00 [%]
p4825 Function generator 2nd amplitude / FG 2nd amplitude
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Trace and function generator Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 0
Min Max Factory setting
-1600.00 [%] 1600.00 [%] 7.00 [%]