2 Parameters
2.2 List of parameters
SINAMICS DCM
360 List Manual (LH8), 02/2015, 6RX1800-0ED76
Description: Sets the target topology of the drive unit.
The target topology is sub-divided into several sections. Each of the following data is saved under an index.
General data on the topology:
- version
- attribute to compare the actual topology and target topology
- number of components
Data on a component:
- type component of the Node Identifier of the component
- number of DRIVE-CLiQ sockets in the Node Identifier
- manufacturer and version of the Node Identifier
- serial number of the Node Identifier (4 indices)
- index of the component
- order number (8 indices)
- attribute to compare the actual topology and target topology of the component
- component number
- number of port types
- port type
- number of ports of the port type
- component number of the associated/linked component
- number of the associated/linked port
- component number of the associated/linked component
- number of the associated port, etc.
Data on the next component:
- etc.
Dependency: Refer to: p9902
Note: The target topology can only be modified using the commissioning software.
The parameter is not displayed for the STARTER commissioning software.
Changes only become effective when the state of p0009 = 101 changes to 0 or 111.
Description: If, when comparing the actual topology and target topology, only error has occurred, that can be acknowledged, then
using this parameter, a new comparison can be started - acknowledging the error in the target topology.
Differences that can be acknowledged:
- topology comparison, component shifted
- topology comparison, serial number of a component has been detected to be different (byte 3 = 1)
- topology comparison shows one component that is connected differently
p9903[0...n] Target topology / Target topo
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: p9902 Func. diagram: -
P-Group: Topology Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 0
Min Max Factory setting
0000 hex FFFF hex 0000 hex
p9904 Topology comparison acknowledge differences / Topo_compare ackn
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: C1(1) Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Topology Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0000 hex FFFF FFFF hex 0000 hex