SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
409
2 Parameters
2.2 List of parameters
Description: Sets the starting behavior for I2t monitoring of the motor.
Value: 2: Start I2t with zero
12: Start I2t with saved value
Note: If value = 12:
For motor I2t monitoring, when switching off, the model temperature is saved in a non-volatile fashion. When
switching on, the saved value is taken into account in the model calculation. As a consequence, the UL508C
specification is fulfilled.
Description: Sets the inverter stability limit for the firing angle of the armature converter in single-phase operation.
Dependency: Refer to: r53190
Note: The status of the Alpha W limit is shown in r53190.8.
Description: Setting of the correction angle for current-dependent offset of the Alpha W limit.
Description: Sets the rectifier stability limit for the firing angle of the armature converter.
Dependency: Refer to: r53190
Note: The status of the Alpha G limit is shown in r53190.7.
p50140 Motor I2t monitoring starting behavior / Mot I2t strt behav
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: - Func. diagram: 8038
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
2 12 12
p50148[0...n] Armature converter Alpha W limit (single-phase operation) / A Alpha W lim 1-ph
DC_CTRL Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6860
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
120.0 [°] 180.0 [°] 178.0 [°]
p50149[0...n] Armature converter correction angle Alpha W limit / Arm corr Alpha W
DC_CTRL Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6860
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-60.0 [°] 0.0 [°] 0.0 [°]
p50150[0...n] Armature converter Alpha G limit / Arm Alpha G lim
DC_CTRL Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6860
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.0 [°] 165.0 [°] 30.0 [°]