2 Parameters
2.2 List of parameters
Description: Setting to activate the intermittent adaptation for the armature current controller.
Value: 0: Intermittent adaptation effective
1: Fixed value 100 %
Dependency: Refer to: p50570, p50571, r52350
Description: Setting to limit the armature current controller adaptation.
Dependency: Refer to: p50571, p50572, r52350
Description: Sets the Kp increase for the intermittent adaptation for the armature current controller.
Dependency: Refer to: p50572
Description: Sets the input variable for the field current controller adaptation.
Value: 0: If_act r52265
1: If_set r52268
Dependency: Refer to: p50576, p50577
Description: Setting to activate the adaptation of non-linear inductances for the field current controller.
p50572[0...n] Adapt arm curr controller intermittent adapt activation / Adapt Interm Act
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: DDS, p0180 Func. diagram: 6853
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
p50573[0...n] Adaptation armature current controller limiting / Adapt Ia_ctrl lim
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6853
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
1.0 [%] 1000.0 [%] 200.0 [%]
p50574[0...n] Adapt arm curr controller intermittent adapt Kp increase / Ad Interm Kp incr
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6853
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.0 10.0 1.0
p50575[0...n] Adaptation field current controller changeover input / Adapt If chgov inp
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: DDS, p0180 Func. diagram: 6908
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
p50576[0...n] Adaptation field current controller non-linear L activation / Adapt n_lin act
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: DDS, p0180 Func. diagram: 6908
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0