EasyManua.ls Logo

Siemens SINAMICS DCM - Adapt Arm Curr Controller Intermittent Adapt Activation; Adapt Arm Curr Controller Intermittent Adapt Kp Increase; Adaptation Armature Current Controller Limiting; Adapt Ia_Ctrl Lim; Adaptation Field Current Controller Changeover Input

Siemens SINAMICS DCM
1204 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
479
2 Parameters
2.2 List of parameters
Description: Setting to activate the intermittent adaptation for the armature current controller.
Value: 0: Intermittent adaptation effective
1: Fixed value 100 %
Dependency: Refer to: p50570, p50571, r52350
Description: Setting to limit the armature current controller adaptation.
Dependency: Refer to: p50571, p50572, r52350
Description: Sets the Kp increase for the intermittent adaptation for the armature current controller.
Dependency: Refer to: p50572
Description: Sets the input variable for the field current controller adaptation.
Value: 0: If_act r52265
1: If_set r52268
Dependency: Refer to: p50576, p50577
Description: Setting to activate the adaptation of non-linear inductances for the field current controller.
p50572[0...n] Adapt arm curr controller intermittent adapt activation / Adapt Interm Act
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: DDS, p0180 Func. diagram: 6853
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
p50573[0...n] Adaptation armature current controller limiting / Adapt Ia_ctrl lim
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6853
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
1.0 [%] 1000.0 [%] 200.0 [%]
p50574[0...n] Adapt arm curr controller intermittent adapt Kp increase / Ad Interm Kp incr
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6853
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.0 10.0 1.0
p50575[0...n] Adaptation field current controller changeover input / Adapt If chgov inp
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: DDS, p0180 Func. diagram: 6908
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
p50576[0...n] Adaptation field current controller non-linear L activation / Adapt n_lin act
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: DDS, p0180 Func. diagram: 6908
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0

Table of Contents

Other manuals for Siemens SINAMICS DCM

Related product manuals