2 Parameters
2.2 List of parameters
Note: If the STW1 is not transferred according to the PROFIdrive with PZD1 (with bit 10 "master control by PLC"), then
p2037 should be set to 2.
Description: Sets the interface mode of the PROFIdrive control words and status words.
When selecting a telegram via p0922 (p2079), this parameter influences the device-specific assignment of the bits in
the control and status words.
Value: 0: SINAMICS
2: VIK-NAMUR
Dependency: Refer to: p0922, p2079
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the serial interface for the debug monitor.
With p2039 = 1, the serial interface COM2 (X179) is set.
Other values are not permitted.
Description: Sets the monitoring time to monitor the process data received via the fieldbus interface.
If no process data is received within this time, then an appropriate message is output.
Note: p2040 = 0:
Monitoring is de-activated.
Description: Sets the PROFIBUS Ident Number (PNO-ID).
SINAMICS can be operated with various identities on PROFIBUS. This allows the use of a PROFIBUS GSD that is
independent of the device (e.g. PROFIdrive VIK-NAMUR with Ident Number 3AA0 hex).
Value: 0: SINAMICS
1: VIK-NAMUR
Note: Every change only becomes effective after a POWER ON.
p2038 IF1 PROFIdrive STW/ZSW interface mode / PD STW/ZSW IF mode
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed: T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Communications Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 2 0
p2039 Select debug monitor interface / Debug monit select
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: U, T Calculated: - Access level: 4
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Communications Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 3 1
p2040 Fieldbus interface monitoring time / Fieldbus t_monit
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 9310
P-Group: Communications Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 1999999 [ms] 100 [ms]
p2042 PROFIBUS Ident Number / PB Ident No.
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Communications Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0