2 Parameters
2.2 List of parameters
SINAMICS DCM
506 List Manual (LH8), 02/2015, 6RX1800-0ED76
Note: 1 signal:
Analog input is enabled
0 signal:
Analog input is disabled (value = 0%)
Description: Sets the setpoint for the simulation of analog input 2 (X177.29/30) on the CUD.
Dependency: Refer to: p50729
Note: Simulation is selected using p50729 = 1.
Description: Setting to select the simulation of analog input 2 (X177.29/30) on the CUD.
Value: 0: Simulation deactivated
1: Simulation activated
Dependency: Refer to: p50727
Note: The setpoint for the simulation is set in p50727.
Description: Sets the scaling for fast analog inputs "Select input 3 to 6".
The value indicates the percentage value for the mapping of an input voltage of 10 V at the analog input.
Example:
p50731[2] = 90%
--> 10 V is scaled to 90% for select input 5
--> 5 V corresponds to 45% for select input 5
Index: [0] = Select input 3 (X177.1/2)
[1] = Select input 4 (X177.3/4)
[2] = Select input 5 (X177.5/6)
[3] = Select input 6 (X177.7/8)
Note: AI: Analog Input
p50727 CUD analog input 2 simulation setpoint / CUD AI 2 sim setp
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 2080
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
-130.0 [%] 130.0 [%] 0.0 [%]
p50729 CUD analog input 2 simulation selection / CUD AI 2 sim sel
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: - Func. diagram: 2080
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
p50731[0...3] Fast analog inputs scaling / Fast AI scal
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 2085, 2090
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
-1000.0 [%] 1000.0 [%] 100.0 [%]