2 Parameters
2.2 List of parameters
SINAMICS DCM
216 List Manual (LH8), 02/2015, 6RX1800-0ED76
Description: Sets the bidirectional digital inputs/outputs as input or output on the Terminal Module 31 (TM31).
Note: DI/DO: Bidirectional Digital Input/Output
Description: Sets the signal source for terminal DI/DO 0 (X520.2) of Terminal Module 15 (TM15).
Note: Prerequisite: The DI/DO must be set as an output (p4028.0 = 1).
DI/DO: Bidirectional Digital Input/Output
Description: Sets the signal source for the digital output DO 0 (X542.1, X542.2, X542.3) of Terminal Module 31 (TM31).
Digital output 0 of TM31 is a relay output.
If the signal at the binector input p4030 is low, then terminal COM 0 (X542.2) is connected to NC 0 (X542.1). This
connection also matches the mechanical quiescent setting of the relay.
If the signal at the binector input p4030 is high, then terminal COM 0 (X542.2) is connected to NO 0 (X542.3).
Note: DO: Digital Output
NC: Normally Closed contact
NO: Normally Open contact
Description: Sets the signal source for terminal DI/DO 1 (X520.3) of Terminal Module 15 (TM15).
Note: Prerequisite: The DI/DO must be set as an output (p4028.1 = 1).
DI/DO: Bidirectional Digital Input/Output
p4028 TM31 set input or output / TM31 DI or DO
TM31 Can be changed: T Calculated: - Access level: 1
Data type: Unsigned32 Dyn. index: - Func. diagram: 9549, 9560,
9562
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 0000 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
08 DI/DO 8 (X541.2) Output Input -
09 DI/DO 9 (X541.3) Output Input -
10 DI/DO 10 (X541.4) Output Input -
11 DI/DO 11 (X541.5) Output Input -
p4030 BI: TM15DI/DO signal source for terminal DI/DO 0 / TM15D s_srcDI/DO 0
TM15DI_DO Can be changed: U, T Calculated: - Access level: 1
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 9399, 9400
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p4030 BI: TM31 signal source for terminal DO 0 / TM31ssDO0
TM31 Can be changed: U, T Calculated: - Access level: 1
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 9549, 9556
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p4031 BI: TM15DI/DO signal source for terminal DI/DO 1 / TM15D s_src DI/DO1
TM15DI_DO Can be changed: U, T Calculated: - Access level: 1
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 9400
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0