4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCM
1142 List Manual (LH8), 02/2015, 6RX1800-0ED76
Reaction upon N: NONE
Acknowl. upon N: NONE
Reaction upon A: NONE
Acknowl. upon A: NONE
F60012 (N, A) P2P-IF: Telegram monitoring time expired
Message value: -
Message class: Communication error to the higher-level control system (9)
Drive object: DC_CTRL
Reaction: OFF2 (NONE, OFF1, OFF3)
Acknowledge: IMMEDIATELY
Cause: The telegram monitoring time for communication via the peer-to-peer interface (P2P-IF) has expired.
No further valid telegrams were received during the monitoring time (p50797).
Possible causes:
- Break in connecting cable
- Electromagnetic interference on the connecting cable
- Telegram monitoring time set too short (p50797)
Remedy: - Check connecting cable and cable connection.
- Check that the connecting cable has been routed in compliance with EMC.
- Increase the telegram monitoring time if necessary (p50797).
See also: p50089 (Sequence control voltage at power unit wait time), p50790 (P2P IF operating mode), p50797 (P2P
IF telegram monitoring time)
Reaction upon N: NONE
Acknowl. upon N: NONE
Reaction upon A: NONE
Acknowl. upon A: NONE
F60014 (N, A) Parallel interface telegram monitoring time expired
Message value: -
Message class: Communication error to the higher-level control system (9)
Drive object: DC_CTRL
Reaction: OFF2 (NONE, OFF1, OFF3)
Acknowledge: IMMEDIATELY
Cause: The telegram monitoring time for communication via the parallel interface (Par-IF) has expired.
No further valid telegrams were received during the monitoring time (p51807).
Possible causes:
- Break in connecting cable
- Electromagnetic interference on the connecting cable
- Telegram monitoring time set too short (p51807)
Remedy: - Check connecting cable and cable connection.
- Check that the connecting cable has been routed in compliance with EMC.
- Increase the telegram monitoring time if necessary (p51807).
See also: p51807 (Parallel interface telegram monitoring failure time), p51808 (Parallel interface signal source for
F60014)
Reaction upon N: NONE
Acknowl. upon N: NONE
Reaction upon A: NONE
Acknowl. upon A: NONE
A60018 (F, N) Digital output overloaded
Message value: Fault cause: %1 bin
Message class: Ground fault / inter-phase short-circuit detected (7)
Drive object: DC_CTRL
Reaction: NONE
Acknowledge: NONE
Cause: At least one digital output is overloaded or has short-circuited.

Table of Contents

Other manuals for Siemens SINAMICS DCM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS DCM and is the answer not in the manual?

Siemens SINAMICS DCM Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS DCM
CategoryMedia Converter
LanguageEnglish

Related product manuals