SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
919
4 Faults and alarms
4.2 List of faults and alarms
F01510 BICO: Signal source is not float type
Message value: Parameter: %1
Message class: Error in the parameterization / configuration / commissioning procedure (18)
Drive object: All objects
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: The requested connector output does not have the correct data type. This interconnection is not established.
Fault value (r0949, interpret decimal):
Parameter number to which an interconnection should be made (connector output).
Remedy: Interconnect this connector input with a connector output having a float data type.
F01511 (A) BICO: Interconnection with different scalings
Message value: Parameter: %1
Message class: Error in the parameterization / configuration / commissioning procedure (18)
Drive object: All objects
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: The requested BICO interconnection was established. However, a conversion is made between the BICO output and
BICO input using the reference values.
- the BICO output has different normalized units than the BICO input.
- message only for interconnections within a drive object.
Example:
The BICO output has, as normalized unit, voltage and the BICO input has current.
This means that the factor p2002/p2001 is calculated between the BICO output and the BICO input.
p2002: contains the reference value for current
p2001: contains the reference value for voltage
Fault value (r0949, interpret decimal):
Parameter number of the BICO input (signal sink).
Remedy: Not necessary.
Reaction upon A: NONE
Acknowl. upon A: NONE
F01512 BICO: No scaling available
Message value: %1
Message class: Error in the parameterization / configuration / commissioning procedure (18)
Drive object: All objects
Reaction: OFF2
Acknowledge: POWER ON
Cause: An attempt was made to determine a conversion factor for a scaling that does not exist.
Fault value (r0949, interpret decimal):
Unit (e.g. corresponding to SPEED) for which an attempt was made to determine a factor.
Remedy: Apply scaling or check the transfer value.
F01513 (N, A) BICO: Interconnection cross DO with different scalings
Message value: Parameter: %1
Message class: Error in the parameterization / configuration / commissioning procedure (18)
Drive object: All objects
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: The requested BICO interconnection was established. However, a conversion is made between the BICO output and
BICO input using the reference values.
An interconnection is made between different drive objects and the BICO output has different normalized units than
the BICO input or the normalized units are the same but the reference values are different.

Table of Contents

Other manuals for Siemens SINAMICS DCM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS DCM and is the answer not in the manual?

Siemens SINAMICS DCM Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS DCM
CategoryMedia Converter
LanguageEnglish

Related product manuals