2 Parameters
2.2 List of parameters
SINAMICS DCM
228 List Manual (LH8), 02/2015, 6RX1800-0ED76
Description: Sets the noise suppression window of the analog inputs for Terminal Module31 (TM31).
Changes less than the window are suppressed.
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Note: AI: Analog Input
Description: Sets the signal source for the enable signal of the analog inputs of Terminal Module 31 (TM31).
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Description: Sets the signal source for the analog outputs of Terminal Module 31 (TM31).
Index: [0] = AO 0 (X522.1, X522.2, X522.3)
[1] = AO 1 (X522.4, X522.5, X522.6)
Note: AO: Analog Output
Description: Displays the actual referred output value of the analog outputs of Terminal Module 31 (TM31).
Index: [0] = AO 0 (X522.1, X522.2, X522.3)
[1] = AO 1 (X522.4, X522.5, X522.6)
p4068[0...1] TM31 analog inputs window to suppress noise / TM31 AI window
TM31 Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 9566, 9568
P-Group: Terminals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [%] 20.00 [%] 0.00 [%]
p4069[0...1] BI: TM31 analog inputs signal source for enable / TM31 AI enable
TM31 Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 9566, 9568
P-Group: Terminals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 1
p4071[0...1] CI: TM31 analog outputs signal source / TM31 AO s s
TM31 Can be changed: U, T Calculated: - Access level: 1
Data type: Unsigned32 / FloatingPoint32 Dyn. index: - Func. diagram: 9549, 9572
P-Group: Terminals Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- - 0
r4072[0...1] TM31 analog outputs output value currently referred / TM31 AO outp_val
TM31 Can be changed: - Calculated: - Access level: 1
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 9572
P-Group: Terminals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]