2 Parameters
2.2 List of parameters
SINAMICS DCM
502 List Manual (LH8), 02/2015, 6RX1800-0ED76
Value: 0: No synchronized analog inputs
1: 6 synchronized analog inputs on left-hand CUD
2: 6 synchronized analog inputs on right-hand CUD
3: 6 synchronized analog inputs on left-hand and right-hand CUD
Notice: This parameter must always be set to the same value on both CUDs!
Note: If value = 0:
There is no quasi-synchronization of the analog inputs on the two CUDs. Connector outputs r52030[0 to 6] on both
CUDs always indicate a value of 0%.
If value = 1:
The analog inputs of the right-hand CUD are interpolated on the left-hand CUD in such a way that 6 simultaneously
scanned values appear at the connector outputs r52030[0 to 6] of the left-hand CUD. Connector outputs r52030[0 to
6] on the right-hand CUD always indicate a value of 0%.
If value = 2:
The analog inputs of the left-hand CUD are interpolated on the right-hand CUD in such a way that 6 simultaneously
scanned values appear at the connector outputs r52030[0 to 6] of the right-hand CUD. Connector outputs r52030[0 to
6] on the left-hand CUD always indicate a value of 0%.
If value = 3:
The analog inputs of the right-hand CUD are interpolated on the left-hand CUD in such a way that 6 simultaneously
scanned values appear at the connector outputs r52030[0 to 6] of the left-hand CUD.
The analog inputs of the left-hand CUD are interpolated on the right-hand CUD in such a way that 6 simultaneously
scanned values appear at the connector outputs r52030[0 to 6] of the right-hand CUD.
Description: Setting to select the simulation of analog input 0 (X177.25/26) on the CUD.
Value: 0: Simulation deactivated
1: Simulation activated
Dependency: Refer to: p50707
Note: The setpoint for the simulation is set in p50707.
Description: Sets the type for analog input 1 (X177.27/28) on the CUD.
Value: 0: Bipolar voltage input (-10 V ... +10 V)
1: Bipolar current input (-20 mA to +20 mA)
2: Unipolar current input monitored (+4 mA to +20 mA)
Note: AI: Analog Input
Description: Sets the scaling for analog input 1 (X177.27/28) on the CUD.
p50709 CUD analog input 0 simulation selection / CUD AI 0 sim sel
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: - Func. diagram: 2075
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
p50710 CUD analog input 1 type / CUD AI 1 type
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: - Func. diagram: 2080
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 2 0
p50711[0...n] CUD analog input 1 scaling / CUD AI 1 scal
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 2080
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
-1000.0 [%] 1000.0 [%] 100.0 [%]