SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
539
2 Parameters
2.2 List of parameters
Description: Sets the signal source for changing over to setpoint step S4 on the 4-step master switch.
Description: Sets the setpoint for setpoint step S1 on the 4-step master switch.
Description: Sets the setpoint for setpoint step S2 on the 4-step master switch.
Description: Sets the setpoint for setpoint step S3 on the 4-step master switch.
Description: Sets the setpoint for setpoint step S4 on the 4-step master switch.
p51664 BI: Signal source for master switch setpoint step S4 / Set step S4 sig s
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 3105
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p51665 Master switch setpoint step S1 value / Set step S1 value
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 3105
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
0.00 [%] 110.00 [%] 10.00 [%]
p51666 Master switch setpoint step S2 value / Set step S2 value
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 3105
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
0.00 [%] 110.00 [%] 25.00 [%]
p51667 Master switch setpoint step S3 value / Set step S3 value
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 3105
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
0.00 [%] 110.00 [%] 40.00 [%]
p51668 Master switch setpoint step S4 value / Set step S4 value
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 3105
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
0.00 [%] 110.00 [%] 100.00 [%]