SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
555
2 Parameters
2.2 List of parameters
Note: The parameter can only be changed for the Control Module.
If value = 1:
The input signal is available via binector output r53140.4 for further interconnection.
If value = 2:
The input signal is available via binector output r53140.3 for further interconnection.
Description: Sets the signal source for the "Fan On" relay output (terminal 120/121) on the power interface.
Note: The parameter can only be changed for the Control Module.
Description: Sets the delay times for device fan monitoring on the Control Module.
Index: [0] = ON delay monitoring
[1] = ON delay fault
[2] = ON delay alarm
Dependency: Refer to: A60266, F60267
Note: The parameter can only be changed for the Control Module.
Description: Sets the rated direct current of an external field device (if there is one).
Dependency: Refer to: p50082
Note: This parameter is only effective if p50082 >= 21.
Description: Setting for activating/de-activating the monitoring for the external field.
Value: 0: Deactivated
1: Activated
p51834 BI: Signal source for device fan relay output / Fan relay sig s
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 6965, 8049
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p51835[0...2] Delay times for device fan monitoring / Fan mon t_del
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 8049
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.0 [s] 60.0 [s] [0] 15.0 [s]
[1] 5.0 [s]
[2] 2.0 [s]
p51838 Field device external rated direct current / I_rated ext
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6960, 6910
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [A] 600.00 [A] 0.00 [A]
p51839 External field monitoring / Ext field monit
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: - Func. diagram: 8044
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0