SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
485
2 Parameters
2.2 List of parameters
About [5]:
Selects which parameter is injected as the variable current limit in torque direction II.
Scaling: +100% corresponding to r50072[1].
About [6]:
Selects which parameter is injected as the current limit in torque direction II for quick stop or shutdown.
Scaling: +100% corresponding to r50072[1].
Description: Sets the signal source for the variable positive torque limit.
Note: Scaling:
[0 to 3] = 100% of the parameter value corresponds to the positive system torque limit according to Ia = p50171.
[4] = 100% of the parameter value corresponds to the positive torque limit according to Ia =r50072[1].
Description: Sets the signal source for the variable negative torque limit.
Note: Scaling:
[0 to 3] = 100% of the parameter value corresponds to the negative system torque limit according to Ia = p50171.
[4] = 100% of the parameter value corresponds to the negative torque limit according to Ia =r50072[1].
Description: Sets the signal source for the master drive's torque setpoint.
Description: Sets the signal source for the torque direction setpoint for the auto-reversing stage.
p50605[0...4] CI: Torque limiting signal source for positive torque limit / T lim pos sig s
DC_CTRL Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dyn. index: - Func. diagram: 6825
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- - 52002[0]
p50606[0...4] CI: Torque limiting signal source for negative torque limit / T lim neg sig s
DC_CTRL Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dyn. index: - Func. diagram: 6825
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- - [0] 52138[0]
[1] 52138[1]
[2] 52138[2]
[3] 52138[3]
[4] 52138[4]
p50607[0...n] CI: Torque limiting signal source for master drive t_set / Mst tq set sig s
DC_CTRL Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dyn. index: CDS, p0170 Func. diagram: 6830
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- - 52148[0]
p50608 CI: Auto-reversing stage signal source for torque direction setpoint / Tqe dir set sig s
DC_CTRL Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dyn. index: - Func. diagram: 6860
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- - 52119[0]