EasyManuals Logo

Siemens SINAMICS DCM List Manual

Siemens SINAMICS DCM
1204 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #449 background imageLoading...
Page #449 background image
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
449
2 Parameters
2.2 List of parameters
Description: Sets the threshold for the maximum speed in positive direction of rotation.
Dependency: Refer to: p50381, p50595, r53025
Refer to: F60038
Note: The "Overspeed" message is available as follows:
- F60038
- r53025.10 (not inverted)
- r53025.11 (inverted)
Description: Sets the threshold for the maximum speed in negative direction of rotation.
Dependency: Refer to: p50380, p50595, r53025
Refer to: F60038
Note: The "Overspeed" message is available as follows:
- F60038
- r53025.10 (not inverted)
- r53025.11 (inverted)
Description: Sets the threshold for the "Setpoint/actual value deviation 1 reached" message.
Dependency: Refer to: p50389, p50390, p50590, p50591, r53025
Refer to: F60031
Note: The "Setpoint/actual value deviation 1 reached" message is available as follows:
- F60031
- r53025.0 (not inverted)
- r53025.1 (inverted)
p50380[0...n] Messages for overspeed threshold positive direction of rotation / Msg n_over pos
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 8025
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
0.0 [%] 200.0 [%] 120.0 [%]
p50381[0...n] Messages for overspeed threshold negative direction of rotation / Msg n_over neg
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 8025
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
-200.0 [%] 0.0 [%] -120.0 [%]
p50388[0...n] Messages for setpoint/actual value deviation 1 threshold / Set/act 1 thresh
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 8020
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
0.00 [%] 200.00 [%] 3.00 [%]

Table of Contents

Other manuals for Siemens SINAMICS DCM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS DCM and is the answer not in the manual?

Siemens SINAMICS DCM Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS DCM
CategoryMedia Converter
LanguageEnglish

Related product manuals