2 Parameters
2.2 List of parameters
SINAMICS DCM
408 List Manual (LH8), 02/2015, 6RX1800-0ED76
Description: Setting of the field current for a motor flux of 80 %.
Note: This parameter is set automatically during the optimization run for field weakening (p50051 = 27).
Only values greater than p50135 and less than p50137 can be set.
Description: Setting of the field current for a motor flux of 85 %.
Note: This parameter is set automatically during the optimization run for field weakening (p50051 = 27).
Only values greater than p50136 and less than p50138 can be set.
Description: Setting of the field current for a motor flux of 90 %.
Note: This parameter is set automatically during the optimization run for field weakening (p50051 = 27).
Only values greater than p50137 and less than p50139 can be set.
Description: Setting of the field current for a motor flux of 95%.
Note: This parameter is set automatically during the optimization run for field weakening (p50051 = 27).
Only values greater than p50138 can be set.
p50136[0...n] Field current for motor flux 80 % / I_field flux 80%
DC_CTRL Can be changed: T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6900, 6910
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
0.0 [%] 100.0 [%] 64.9 [%]
p50137[0...n] Field current for motor flux 85 % / I_field flux 85%
DC_CTRL Can be changed: T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6900, 6910
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
0.0 [%] 100.0 [%] 71.8 [%]
p50138[0...n] Field current for motor flux 90 % / I_field flux 90%
DC_CTRL Can be changed: T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6900, 6910
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
0.0 [%] 100.0 [%] 79.8 [%]
p50139[0...n] Field current for motor flux 95% / I_field flux 95%
DC_CTRL Can be changed: T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6900, 6910
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
0.0 [%] 100.0 [%] 89.1 [%]