2 Parameters
2.2 List of parameters
SINAMICS DCM
44 List Manual (LH8), 02/2015, 6RX1800-0ED76
Description: Displays actual absolute current.
Index: [0] = Unsmoothed
[1] = Smoothed with p0045
Dependency: Refer to: r0027, p0045
Note: The absolute value of the current actual value is available smoothed (r0027 with 100 ms, r0068[1] with p0045) and
unsmoothed (r0068[0]).
Description: Display and connector output for actual torque value.
Index: [0] = Unsmoothed
[1] = Smoothed with p0045
Dependency: Refer to: r0031, p0045
Note: The value is available smoothed (r0031 with 100 ms, r0080[1] with p0045) and unsmoothed (r0080[0]).
Description: Displays the instantaneous active power.
Index: [0] = Unsmoothed
[1] = Smoothed with p0045
Dependency: Refer to: r0032
Note: The active power is available smoothed (r0032 with 100 ms, r0082[1] with p0045) and unsmoothed (r0082[0]).
Description: Executes an automatic device configuration.
In so doing, p0099, p0107 and p0108 are appropriately set.
Value: 0: No selection
15: Drive object type DC_CTRL
Dependency: Refer to: r0098, p0099
Note: For p0097 = 0, p0099 is automatically set to the factory setting.
r0068[0...1] CO: Absolute current actual value / I_act abs val
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6850
P-Group: Displays, signals Unit group: - Unit selection: -
Not for motor type: - Scaling: p2002 Expert list: 1
Min Max Factory setting
- [A] - [A] - [A]
r0080[0...1] CO: Torque actual value / M_act
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6850
P-Group: Displays, signals Unit group: 7_1 Unit selection: p0505
Not for motor type: - Scaling: p2003 Expert list: 1
Min Max Factory setting
- [Nm] - [Nm] - [Nm]
r0082[0...1] CO: Active power actual value / P_act
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Displays, signals Unit group: 14_5 Unit selection: p0505
Not for motor type: - Scaling: r2004 Expert list: 1
Min Max Factory setting
- [kW] - [kW] - [kW]
p0097 Select drive object type / Select DO type
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: C1(1) Calculated: - Access level: 1
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Topology Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 15 0