SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
163
2 Parameters
2.2 List of parameters
Description: Selects the faults for which the fault response should be changed
Dependency: The fault is selected and the required response is set under the same index.
Refer to: p2101
Note: Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
Description: Sets the fault response for the selected fault.
Value: 0: NONE
Dependency: The fault is selected and the required response is set under the same index.
Notice: For the following cases, it is not possible to re-parameterize the fault response to a fault:
- Fault number does not exist (exception value = 0).
- Message type is not "fault" (F).
- Fault response is not permissible for the set fault number.
Note: Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
Description: Sets the fault response for the selected fault.
Value: 0: NONE
1: OFF1
2: OFF2
3: OFF3
5: Reserved
6: Reserved
7: Reserved
Dependency: The fault is selected and the required response is set under the same index.
Refer to: p2100
Notice: For the following cases, it is not possible to re-parameterize the fault response to a fault:
- Fault number does not exist (exception value = 0).
- Message type is not "fault" (F).
- Fault response is not permissible for the set fault number.
p2100[0...19] Change fault response fault number / Chng resp F_no
TM150, TM15DI_DO,
TM31
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: 8050, 8075
P-Group: Messages Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 65535 0
p2101[0...19] Change fault response response / Chng resp resp
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: 8075
P-Group: Messages Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 0 0
p2101[0...19] Change fault response response / Chng resp resp
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: 8075
P-Group: Messages Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 7 0