SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
465
2 Parameters
2.2 List of parameters
Description: Sets the time during which setpoint 2 should be applied for the square-wave generator.
Dependency: Refer to: p50480, p50481, p50482
Description: Sets the signal source for the default setpoint for oscillation.
This setpoint is injected when the "Oscillate" function is not selected.
Dependency: Refer to: p50485
Description: Sets the signal source for the selection of the "Oscillate" function.
Dependency: Refer to: p50480, p50481, p50482, p50483, p50484
Note: BI: p50485 = 0 signal
Oscillation is not selected. The default setpoint is applied (CI: p50484).
BI: p50485 = 1 signal
Oscillation is selected. The square-wave generator is active (p50480, p50481, p50482, p50483).
Description: Sets the signal source for triggering fault F60025 "Brush length".
Dependency: Refer to: r53120
Refer to: F60025
Note: The fault is triggered with a delay.
The signal is available via binector output r53210.0 for further interconnection.
p50483[0...n] Oscillation setpoint 2 time / Oscill set 2 t
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 3120
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.1 [s] 300.0 [s] 0.1 [s]
p50484[0...n] CI: Oscillation signal source for default setpoint / Oscill def set
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: Unsigned32 / FloatingPoint32 Dyn. index: CDS, p0170 Func. diagram: 3120
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- - 52209[0]
p50485[0...n] BI: Oscillation selection of signal source / Oscill sel sig s
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: Unsigned32 / Binary Dyn. index: CDS, p0170 Func. diagram: 3120
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p50486 BI: Motor interface signal source for brush length / Mot br l sig s
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 8035
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0