2 Parameters
2.2 List of parameters
SINAMICS DCM
182 List Manual (LH8), 02/2015, 6RX1800-0ED76
Description: Sets the signal source to switch in/switch out the technology controller.
The technology controller is switched in with a 1 signal.
Description: Sets the configuration of the technology controller.
Dependency: Refer to: p2257, p2258, p2267, p2268, p2280, p2285
Note: Re bit 00 = 0:
The ramp-down time (p2258) switches to the ramp-up time (p2257) when the sign for the output signal r2260
changes. When the sign changes, the output signal is kept at zero for one arithmetic cycle.
Re bit 00 = 1:
When r2260 exhibits a positive gradient, the ramp-up time (p2257) is active; when it exhibits a negative gradient, the
ramp-down time (p2258) is active. The sign for r2260 does not have any effect on the ramp time.
Re bit 01 = 0:
The integration time of the PID controller is evaluated with the gain factor Kp (p2280) (p2285 = integral time).
Re bit 01 = 1:
The integration time of the PID controller is independent of the gain factor (p2285 = integration time) if p2280 > 0.
Re bit 02 = 0:
When the PID controller is de-activated via p2200, the output signal r2294 is reduced to zero via the ramp-down time
p2293.
Re bit 02 = 1:
When the PID controller is de-activated via p2200, the output signal r2294 is set directly to zero.
Re bit 03 = 0:
The actual values are not limited by p2267 and p2268.
Re bit 03 = 1:
The actual values are limited by p2267 and p2268.
Description: Sets the signal source for the setpoint 1 of the technology controller.
Dependency: Refer to: p2254, p2255
p2200[0...n] BI: Technology controller enable / Tec_ctrl enable
DC_CTRL (Tech_ctrl),
DC_CTRL_R
(Tech_ctrl),
DC_CTRL_R_S
(Tech_ctrl),
DC_CTRL_S
(Tech_ctrl)
Can be changed: T Calculated: - Access level: 2
Data type: Unsigned32 / Binary Dyn. index: CDS, p0170 Func. diagram: 7958
P-Group: Technology Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p2252 Technology controller configuration / Tec_ctrl config
DC_CTRL (Tech_ctrl),
DC_CTRL_R
(Tech_ctrl),
DC_CTRL_R_S
(Tech_ctrl),
DC_CTRL_S
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Modulation Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0111 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Ramp-up/down time independent of
setpoint sign
Yes No -
01 Integrator independent of Kp Yes No -
02 Output signal without ramp active Yes No -
03 Actual value limiting Yes No -
p2253[0...n] CI: Technology controller setpoint 1 / Tec_ctrl setp 1
DC_CTRL (Tech_ctrl),
DC_CTRL_R
(Tech_ctrl),
DC_CTRL_R_S
(Tech_ctrl),
DC_CTRL_S
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned32 / FloatingPoint32 Dyn. index: CDS, p0170 Func. diagram: 7958
P-Group: Technology Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- - 0