SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
99
2 Parameters
2.2 List of parameters
Description: Copies one Drive Data Set (DDS) into another.
Index: [0] = Source Drive Data Set
[1] = Target Drive Data Set
[2] = Start copying procedure
Note: Procedure:
1. In Index 0, enter which drive data set is to be copied.
2. In Index 1, enter the drive data set data that is to be copied into.
3. Start copying: Set index 2 from 0 to 1.
p0819[2] is automatically set to 0 when copying is completed.
Description: Sets the signal source to select the Drive Data Set, bit 0 (DDS, bit 0).
Dependency: Refer to: r0051, r0837
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the signal source to select the Drive Data Set, bit 1 (DDS, bit 1).
Dependency: Refer to: r0051, r0837
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Displays the status word for the drive data set changeover.
Note: Re bit 02:
A data set changeover is delayed by the time required for the internal parameter calculation.
p0819[0...2] Copy Drive Data Set DDS / Copy DDS
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed: C2(15) Calculated: - Access level: 2
Data type: Unsigned8 Dyn. index: - Func. diagram: 8565
P-Group: Data sets Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 31 0
p0820[0...n] BI: Drive Data Set selection DDS bit 0 / DDS select., bit 0
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed: C2(15), T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: CDS, p0170 Func. diagram: 8565, 8570
P-Group: Data sets Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p0821[0...n] BI: Drive Data Set selection DDS bit 1 / DDS select., bit 1
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed: C2(15), T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: CDS, p0170 Func. diagram: 8565, 8570
P-Group: Data sets Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
r0835.2 CO/BO: Data set changeover status word / DDS_ZSW
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: 8575
P-Group: Displays, signals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
02 Internal parameter calculation active Yes No -

Table of Contents

Other manuals for Siemens SINAMICS DCM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS DCM and is the answer not in the manual?

Siemens SINAMICS DCM Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS DCM
CategoryMedia Converter
LanguageEnglish

Related product manuals