2 Parameters
2.2 List of parameters
SINAMICS DCM
534 List Manual (LH8), 02/2015, 6RX1800-0ED76
Note: If the test command is issued in operation (i.e. in operating state o0.1 or o0.2), then the turn-off operation of the
SIMOREG CCP acts on the thyristor bridge that is presently enabled. This is independent of whether the turn-off
command is issued in torque direction I or II.
Description: Sets the reduction factor for the current-dependent armature inductance.
At 100% motor rated current (p50100), the armature inductance is lower than it is at armature current 0 by this factor.
Dependency: Refer to: p50111
Note: The parameter is set automatically during the "optimization run for pre-control and the current controller for the
armature converter" (p50051 = 25).
Description: Sets the commutating inductance in the armature circuit.
Description: Sets the inductance of the interphase transformer in 12-pulse operation (two 6-pulse thyristor bridge circuits
connected in parallel).
Dependency: Refer to: p51595
Note: The parameter is set automatically during the "optimization run for pre-control and the current controller for the
armature converter" (p50051 = 25).
Description: Sets the reduction factor for the current-dependent interphase inductance.
At 100% motor rated current (p50100), the interphase inductance is lower than it is at armature current 0 by this
factor.
Dependency: Refer to: p51594
Note: The parameter is set automatically during the "optimization run for pre-control and the current controller for the
armature converter" (p50051 = 25).
p51591[0...n] Armature inductance reduction factor / L_armat red fact
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6854
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
10 [%] 100 [%] 100 [%]
p51592[0...n] Armature commutating inductance / Arm Lk
DC_CTRL Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6854
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.0 [mH] 1000.0 [mH] 0.0 [mH]
p51594[0...n] Interphase inductance in 12-pulse operation / L_intph 12-pulse
DC_CTRL Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6854
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.0 [mH] 1000000.0 [mH] 0.0 [mH]
p51595[0...n] Interphase inductance reduction factor / L_intph red fact
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6854
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
10 [%] 100 [%] 100 [%]