2 Parameters
2.2 List of parameters
SINAMICS DCM
346 List Manual (LH8), 02/2015, 6RX1800-0ED76
If value = 0:
DHCP deactivated.
If value = 1:
Reserved.
If value = 2:
DHCP activated. The MAC address of this interface is used for client identification.
If value = 3:
DHCP activated. The station name of this interface is used for client identification.
Description: Sets the activation of the interface configuration for the Communication Board Ethernet 20/25 (CBE20/CBE25).
p8945 is automatically set to 0 at the end of an operation.
Value: 0: No function
2: Save and activate configuration
3: Delete configuration
Dependency: Refer to: p8940, p8941, p8942, p8943, p8944
Notice: When the DHCP mode is active (p8944 > 0), then PROFINET communication via this interface is no longer possible!
However, the interface can be used by the STARTER/SCOUT commissioning tool.
Note: For CBE20, the parameter is only valid for firmware version "PROFINET Device" (p8835 = 1) or "Ethernet/IP" (p8835
= 4). Otherwise, it is locked.
This restriction is not applicable for the CBE25.
Re p8945 = 2:
The interface configuration (p8940 and following) is saved and activated after the next POWER ON.
Re p8945 = 3:
The factory setting of the interface configuration is loaded after the next POWER ON.
Description: Displays the active station name for the Communication Board Ethernet 20/25 (CBE20/CBE25).
Description: Displays the active IP address for the Communication Board Ethernet 20/25 (CBE20/CBE25).
p8945 CBE2x interface configuration / CBE2x int config
CU_DC (PROFINET
CBE20), CU_DC_R
(PROFINET CBE20),
CU_DC_R_S
(PROFINET CBE20),
CU_DC_S
(PROFINET CBE20)
Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 3 0
r8950[0...239] CBE2x Name of Station active / CBE2x Name act
CU_DC (PROFINET
CBE20), CU_DC_R
(PROFINET CBE20),
CU_DC_R_S
(PROFINET CBE20),
CU_DC_S
(PROFINET CBE20)
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
r8951[0...3] CBE2x IP Address of Station active / CBE2x IP act
CU_DC (PROFINET
CBE20), CU_DC_R
(PROFINET CBE20),
CU_DC_R_S
(PROFINET CBE20),
CU_DC_S
(PROFINET CBE20)
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 255 -