SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
495
2 Parameters
2.2 List of parameters
Description: Sets the signal sources for "Bypass ramp-function generator".
Dependency: Refer to: p50641
Note: The "Bypass ramp-function generator" signal can also be set via binector input p50641.
About index 0, 1, 2 and their factory setting:
The "Bypass ramp-function generator" signal comes from the "Fixed setpoint", "Jog setpoint", "Creep setpoint"
function.
Description: Sets the signal sources for the ramp-function generator's setting value with OFF1.
The ramp-function generator is set to this value once.
Index: [0] = Setting value 1
[1] = Setting value 2
Dependency: The selection of the signal source for the setting value is set via p50318.
p50318 = 0: Do not set ramp-function generator output
p50318 = 1: Set ramp-function generator output to the value supplied via connector input p50650[0].
p50318 = 2: Set ramp-function generator output to the value supplied via connector input p50650[1].
Refer to: p50318
Description: Sets the signal sources for the effective limits for ramp-function generator tracking.
Index: [0] = Scaled motor flux
[1] = Speed actual value
[2] = Effective positive torque limit
[3] = Effective negative torque limit
[4] = Effective positive current limit
p50649[0...2] BI: Bypass ramp-function generator signal source / Bypass RFG sig s
DC_CTRL Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 3152
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - [0] 53170.10
[1] 53170.11
[2] 53170.12
p50650[0...1] CI: RFG signal source for setting value with OFF1 / RFG s v OFF1 sig s
DC_CTRL Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dyn. index: - Func. diagram: 3152
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- - [0] 52167[0]
[1] 52179[0]
p50651[0...6] CI: RFG tracking signal sources / RFG track sig s
DC_CTRL Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dyn. index: - Func. diagram: 3152
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- - [0] 52290[0]
[1] 52167[0]
[2] 52143[0]
[3] 52144[0]
[4] 52131[0]
[5] 52132[0]
[6] 50219[0]