SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
209
2 Parameters
2.2 List of parameters
Description: Displays the counter reading for modified BICO interconnections on this drive object.
The counter is incremented by one for each modified BICO interconnection.
Description: Setting to acknowledge all active faults of a drive object.
Notice: Safety messages cannot be acknowledged using this parameter.
Note: Parameter should be set from 0 to 1 to acknowledge.
After acknowledgement, the parameter is automatically reset to 0.
Description: Sets the mode to change over the master control / LOCAL mode.
Value: 0: Change master control for STW1.0 = 0
1: Change master control in operation
Danger: When changing the master control in operation, the drive can manifest undesirable behavior - e.g. it can accelerate
up to another setpoint.
Description: Displays the number of parameters for this drive unit.
The number comprises the device-specific and the drive-specific parameters.
Dependency: Refer to: r0980, r0981, r0989
r3979 BICO counter drive object / BICO counter DO
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S, TM150,
TM15DI_DO, TM31
Can be changed: - Calculated: - Access level: 4
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
p3981 Faults acknowledge drive object / Faults ackn DO
All objects Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned8 Dyn. index: - Func. diagram: 8060
P-Group: Messages Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
p3985 Master control mode selection / PcCtrl mode select
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Setpoints Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
r3986 Parameter count / Parameter No.
All objects Can be changed: - Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -

Table of Contents

Other manuals for Siemens SINAMICS DCM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS DCM and is the answer not in the manual?

Siemens SINAMICS DCM Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS DCM
CategoryMedia Converter
LanguageEnglish

Related product manuals