2 Parameters
2.2 List of parameters
SINAMICS DCM
362 List Manual (LH8), 02/2015, 6RX1800-0ED76
When comparing the topology, the following data is compared in the target and actual topologies:
p9906 = 0: Component type, Order No., Hardware version, Manufacturer, Serial No.
p9906 = 1: Component type, Order No.
p9906 = 2: Component type
p9906 = 3: Component class (e.g. Sensor Module or Motor Module)
Description: Enters the number of the component where the setting of how the actual topology should be compared to the target
topology should be changed.
Dependency: Refer to: p9908
Description: Sets the type of comparison of a component in the target topology with the actual topology.
The comparison is started by setting the required value.
Value: 0: High: Compares the complete electronic rating plate
1: Average: Compares the component type and the Order number
2: Low: Compares the component type
3: Minimum: Compares the component class
99: Topology has different comparison stages
Dependency: Refer to: p9907
Note: The electronic rating plate comprises the following data:
- component type (e.g. "SMC20")
- Order No. (e.g. "6SL3055-0AA0-5BA0")
- manufacturer (e.g. SIEMENS)
- hardware version (e.g. "A")
- Serial No. (e.g. "T-P30050495")
When comparing the topology, the following data is compared in the target and actual topologies:
p9908 = 0: Component type, Order No., Hardware version, Manufacturer, Serial No.
p9908 = 1: Component type, Order No.
p9908 = 2: Component type
p9908 = 3: Component class (e.g. Sensor Module or Motor Module)
Description: For p9909 = 1, the serial number and the hardware version of the new replaced component is automatically
transferred from the actual topology into the target topology and then saved in a non-volatile fashion.
p9907 Topology comparison comparison stage of the component number /
Topo_cmpr comp_no
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: C1(1) Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: Topology Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 199 0
p9908 Topology comparison comparison stage of a component / Topo_cmpr 1 comp
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: C1(1) Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Topology Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 99 0
p9909 Topology comparison component replacement / Topo_cmpr replace
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: C1(1) Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: Topology Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 1