2.2 List of parameters
Description: Sets the signal source for the digital output DO 1 (X542.4, X542.5, X542.6) of Terminal Module 31 (TM31).
Digital output 1 of TM31 is a relay output.
If the signal at the binector input p4031 is low, then terminal COM 1 (X542.5) is connected to NC 1 (X542.4). This
connection also matches the mechanical quiescent setting of the relay.
If the signal at the binector input p4031 is high, then terminal COM 1 (X542.5) is connected to NO 1 (X542.6).
Note: DO: Digital Output
NC: Normally Closed contact
NO: Normally Open contact
Description: Sets the signal source for terminal DI/DO 2 (X520.4) of Terminal Module 15 (TM15).
Note: Prerequisite: The DI/DO must be set as an output (p4028.2 = 1).
DI/DO: Bidirectional Digital Input/Output
Description: Sets the signal source for terminal DI/DO 3 (X520.5) of Terminal Module 15 (TM15).
Note: Prerequisite: The DI/DO must be set as an output (p4028.3 = 1).
DI/DO: Bidirectional Digital Input/Output
Description: Sets the signal source for terminal DI/DO 4 (X520.6) of Terminal Module 15 (TM15).
Note: Prerequisite: The DI/DO must be set as an output (p4028.4 = 1).
DI/DO: Bidirectional Digital Input/Output
p4031 BI: TM31 signal source for terminal DO 1 / TM31ssDO1
TM31 Can be changed: U, T Calculated: - Access level: 1
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 9549, 9556
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p4032 BI: TM15DI/DO signal source for terminal DI/DO 2 / TM15D s_src DI/DO2
TM15DI_DO Can be changed: U, T Calculated: - Access level: 1
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 9400
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p4033 BI: TM15DI/DO signal source for terminal DI/DO 3 / TM15D s_src DI/DO3
TM15DI_DO Can be changed: U, T Calculated: - Access level: 1
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 9400
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p4034 BI: TM15DI/DO signal source for terminal DI/DO 4 / TM15D s_src DI/DO4
TM15DI_DO Can be changed: U, T Calculated: - Access level: 1
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 9400
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0