2 Parameters
2.2 List of parameters
SINAMICS DCM
344 List Manual (LH8), 02/2015, 6RX1800-0ED76
Dependency: Refer to: r8894, r8895, p8899
Description: Sets the signal source for the connector-binector converter.
A PZD receive word can be selected as signal source. The signals are available to be serially passed-on
(interconnection).
Dependency: Refer to: r8850, r8894, r8895, p8898
Note: From the signal source set via the connector input, the corresponding lower 16 bits are converted.
p8899[0...1] together with r8894.0...15 and r8895.0...15 forms two connector-binector converters:
Connector input p8899[0] to binector output in r8894.0...15
Connector input p8899[1] to binector output in r8895.0...15
Description: Displays the PROFINET Device ID.
Every SINAMICS device type has its own PROFINET Device ID and its own PROFINET GSD.
Note: List of the SINAMICS Device IDs:
0501 hex: S120/S150
0504 hex: G130/G150
050A hex: DC MASTER
050C hex: MV
050F hex: G120P
0510 hex: G120C
0511 hex: G120 CU240E-2
0512 hex: G120D
0513 hex: G120 CU250S-2 Vector
0514 hex: G110M
Description: Sets the station name for the Communication Board Ethernet 20/25 (CBE20/CBE25).
Dependency: Refer to: p8941, p8942, p8943, p8944, p8945
Note: An ASCII table (excerpt) can be found, for example, in the appendix to the List Manual.
The interface configuration (p8940 and following) is activated with p8945.
The parameter is not influenced by setting the factory setting.
p8899[0...1] CI: IF2 connector-binector converter signal source / Con/bin S_src
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Integer16 Dyn. index: - Func. diagram: 2485, 2491
P-Group: Communications Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
r8909 PN device ID / PN device ID
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
p8940[0...239] CBE2x Name of Station / CBE2x Name Stat
CU_DC (PROFINET
CBE20), CU_DC_R
(PROFINET CBE20),
CU_DC_R_S
(PROFINET CBE20),
CU_DC_S
(PROFINET CBE20)
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -