2 Parameters
2.2 List of parameters
SINAMICS DCM
566 List Manual (LH8), 02/2015, 6RX1800-0ED76
Scaling:
0 % corresponds to 0 °C
100 % corresponds to 100 °C
Dependency: The parameter is only valid for the following temperature sensors with a continuous characteristic:
- KTY84 (p50490 = 1)
- PT100 (p50490 = 6)
- NTC thermistor K227 (p50490 = 7)
- PT1000 (p50490 = 8)
Refer to: p50490
Note: If p50490 = 0, 2 to 5, a value of 0 is displayed.
Description: Display and connector output for the armature firing angle after limiting by the auto-reversing stage.
Description: Display and connector output for the armature firing angle before limiting by the auto-reversing stage.
Description: Display and connector output for the output to the armature gating module (pre-control value + armature current
controller output).
Description: Displays the armature current flow duration/time ratio between 2 consecutive firing pulses.
r52100 CO: Armature firing angle after limiting / Fir ang aft lim
DC_CTRL Can be changed: - Calculated: - Access level: 1
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6860
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
r52101 CO: Armature firing angle before limiting / Fir ang bef lim
DC_CTRL Can be changed: - Calculated: - Access level: 1
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6860, 6900
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
r52102 CO: Cl-loop arm curr ctrl prectr value + arm curr controller output / Ia ctr prec+outp
DC_CTRL Can be changed: - Calculated: - Access level: 1
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6855
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
r52103 CO: Armature current flow duration / Arm I_flow dur
DC_CTRL Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6850
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]