SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
939
4 Faults and alarms
4.2 List of faults and alarms
Remedy: Reduce the memory required, e.g. as follows:
- reduce the trace time.
- increase the trace clock cycle.
- reduce the number of signals to be traced.
See also: r4708 (Trace memory space required), r4799 (Trace memory location free)
A02150 OA: Application cannot be loaded
Message value: %1
Message class: Hardware / software error (1)
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: The system was not able to load an OA application.
Alarm value (r2124, interpret hexadecimal):
16:
The interface version in the DCB user library is not compatible to the DCC standard library that has been loaded.
Only for internal Siemens troubleshooting.
Remedy: - carry out a POWER ON (power off/on) for all components.
- upgrade firmware to later version.
- contact the Hotline.
Re alarm value = 16:
Load a compatible DCB user library (compatible to the interface of the DCC standard library).
Note:
OA: Open Architecture
See also: r4950, r4955, p4956, r4957
F02151 (A) OA: Internal software error
Message value: %1
Message class: Hardware / software error (1)
Drive object: All objects
Reaction: OFF2 (NONE, OFF1, OFF3)
Acknowledge: IMMEDIATELY (POWER ON)
Cause: An internal software error has occurred within an OA application.
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy: - carry out a POWER ON (power off/on) for all components.
- upgrade firmware to later version.
- contact the Hotline.
- replace the Control Unit.
Note:
OA: Open Architecture
See also: r4950, r4955, p4956, r4957
Reaction upon A: NONE
Acknowl. upon A: NONE
F02152 (A) OA: Insufficient memory
Message value: %1
Message class: Hardware / software error (1)
Drive object: All objects
Reaction: OFF1
Acknowledge: IMMEDIATELY (POWER ON)
Cause: Too many functions have been configured on this Control Unit (e.g. too many drives, function modules, data sets, OA
applications, blocks, etc).
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.