2 Parameters
2.2 List of parameters
SINAMICS DCM
32 List Manual (LH8), 02/2015, 6RX1800-0ED76
Note: The set access level via p0003 is also relevant for the display filter via p0004.
Examples (assumption: p0009 = p0010 = 0):
p0003 = 1, p0004 = 3
--> Only the parameters for the motor with access level 1 are displayed.
p0003 = 2, p0004 = 3
--> Only the parameters for the motor with access levels 1 and 2 are displayed.
Description: Sets the parameter number and parameter index for display for p0006 = 4 for the Basic Operator Panel (BOP).
Index: [0] = Parameter number
[1] = Parameter index
Dependency: Refer to: p0006
Note: Procedure:
1.
The parameter number to be displayed should be set in index 0. Only the monitoring parameters (read-only
parameters) can be set that actually exist for the actual drive object.
If the set parameter number is not indexed, or if there is an index in index 1 that lies outside the valid range of the set
parameter, then index 1 is automatically set to 0.
2.
The index that belongs to the parameter set in index 0 should be set in index 1. The permissible changes in index 1
always depend on the parameter number set in index 0.
Description: Sets the parameter number and parameter index for display for p0006 = 4 for the Basic Operator Panel (BOP).
Index: [0] = Parameter number
[1] = Parameter index
Dependency: Refer to: p0006
Note: Procedure:
1.
The parameter number to be displayed should be set in index 0. Only the monitoring parameters (read-only
parameters) can be set that actually exist for the actual drive object.
If the set parameter number is not indexed, or if there is an index in index 1 that lies outside the valid range of the set
parameter, then index 1 is automatically set to 0.
2.
The index that belongs to the parameter set in index 0 should be set in index 1. The permissible changes in index 1
always depend on the parameter number set in index 0.
p0005[0...1] BOP operating display selection / BOP op_disp sel
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 65535 [0] 2
[1] 0
p0005[0...1] BOP operating display selection / BOP op_disp sel
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 65535 [0] 50000
[1] 0