4 Faults and alarms
4.2 List of faults and alarms
Note for fault value = 205:
- r50047[1]: Number of required measuring cycles
- r50047[2]: Number of valid measuring cycles
- r50047[3]: Measurement run
Note for fault value = 206:
- r50047[1]: Calculate armature circuit inductance in H
Note for fault value = 301:
- r50047[1]: Number of measuring points (0 to 4 are possible, at least 2 are required)
Note for fault value = 401:
- r50047[1]: Nominal EMF (max. permissible EMF setpoint) (1 = 100 %)
- r50047[1]: Ideal nominal rectifier no-load output voltage (1 = 100 %)
Note for fault value = 402:
- r50047[1]: 1 = Timeout determining nominal speed, 2 = Timeout recording field characteristic
Note for fault value = 403:
- r50047[1]: EMF setpoint (1 = 100 %)
- r50047[2]: EMF actual value (1 = 100 %)
- r50047[3]: Ramp-up monitoring time in s
Note for fault value = 404:
- r50047[1]: Speed actual value (1 = 100 %)
Note for fault value = 405:
- r50047[1]: Index in meas. table
- r50047[2]: Field current setpoint (1 = 100 %)
Note for fault value = 406:
- r50047[1]: Field current setpoint (1 = 100 %)
- r50047[2]: Flux previous measuring point (1 = 100 %)
- r50047[3]: Flux actual measuring point (1 = 100 %)
Note for fault value = 407:
- r50047[1]: Index in meas. table
- r50047[2]: Field current setpoint (1 = 100 %)
Note for fault value = 408:
- r50047[1]: Index in meas. table
- r50047[2]: Field current setpoint (1 = 100 %)
Note for fault value = 409:
- r50047[1]: Index in meas. table
- r50047[2]: Field current setpoint (1 = 100 %)
Note for fault value = 501:
- r50047[1]: Speed setpoint (1 = 100 %)
- r50047[2]: Speed actual value (1 = 100 %)
- r50047[3]: Speed, lower limit (1 = 100 %)
- r50047[4]: Speed, upper limit (1 = 100 %)
- r50047[5]: 0 = No limit active, 1 = Current limit active, 2 = Torque limit active
Note for fault value = 601:
- r50047[1]: speed setpoint (1 = 100 %) according to p50565
- r50047[2]: Speed actual value (1 = 100 %)
- r50047[3]: permissible time in s, until the speed setpoint is reached
Note for fault value = 602:
- r50047[1]: Speed actual value (1 = 100 %)
Note for fault value = 701:
- r50047[1]: P2P/CCP operating mode
Note for fault value = 703:
- r50047[1]: determined index for order number (MLFB)