EasyManua.ls Logo

ABB AC500 PLC - 1.7.6.2.9 Measuring Ranges; Input Ranges Voltage, Current and Digital Input

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1.7.6.2.9 Measuring Ranges
Input Ranges Voltage, Current and Digital Input
Range 0...10 V -10...+10 V 0...20 mA 4...20 mA Digital input
Overflow >11.7589 >11.7589 >23.5178 >22.8142
Measured
value too high
11.7589
:
10.0004
11.7589
:
10.0004
23.5178
:
20.0007
22.8142
:
20.0006
Normal range
Normal range
or measured
value too low
10.0000
:
0.0004
10.0000
:
0.0004
20.0000
:
0.0007
20.0000
:
4.0006
On
0.0000 0.0000 0 4 Off
-0.0004
-1.7593
-0.0004
:
:
:
-10.0000
3.9994
:
0
Measured
value too low
-10.0004
:
-11.7589
Underflow <0.0000 <-11.7589 <0.0000 <0.0000
Range Digital value
Decimal Hex.
Overflow 32767 7FFF
Measured value too high 32511
:
27649
7EFF
:
6C01
Normal range
Normal range or measured
value too low
27648
:
1
6C00
:
0001
0 0000
-1
-4864
-6912
:
-27648
FFFF
ED00
E500
:
9400
Measured value too low -27649
:
-32512
93FF
:
8100
Underflow -32768 8000
The represented resolution corresponds to 16 bits.
Device Specifications
Communication Interface Modules (S500) > PROFINET
2019/04/17 3ADR010121, 13, en_US 1037

Table of Contents