ABB AC500 PLC - Technical Data of the Analog Inputs if Used as Digital Inputs

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Value
Maximum permanent allowed overload (no damage)
Current input When the input current exceeds the
overflow value of the measurement
range, the input impedance is switched
to high impedance for protection. The
maximum allowed overload is then 30 V.
The digital value corresponds to the
overflow value. Periodically, the input
impedance is switched to the normal
value and the input current is measured.
If the input current is within the meas-
urement range, the input impedance
remains at the normal level and the dig-
ital value corresponds to the measured
current.
Voltage input 30 V
Relationship between input signal and hex code
Unused voltage inputs Are configured as "unused"
Unused current inputs Have a low resistance, can be left open-
circuited
Overvoltage protection Yes
Technical Data of the Analog Inputs if Used as Digital Inputs
Parameter Value
Number of channels per module Max. 8
Distribution of channels into groups 2 groups of 4 channels each
Connections of the channels I0+ to I3+
Connections of the channels I4+ to I7+
Terminals 2.0, 2.2, 2.4, 2.6
Terminals 4.0, 4.2, 4.4, 4.6
Reference potential for the inputs Terminals 1.9, 2.9, 3.9 and 4.9 (ZP)
Input delay Typ. 2 ms
Indication of the input signals 1 LED per channel
Input signal voltage 24 VDC
Signal 0 -30 V...+5 V
Undefined signal +5 V...+13 V
Signal 1 +13 V...+30 V
Input current per channel
Input voltage +24 V Typ. 5 mA
Input voltage +5 V Typ. 1 mA
Input voltage +15 V Typ. 3.1 mA
Input voltage +30 V < 7 mA
Input resistance Ca. 4.8 kW
Device Specifications
I/O Modules > Analog I/O Modules
2019/04/173ADR010121, 13, en_US504