1.2.1.3.8 Displays
LED Status Color LED = ON LED = OFF
DI0...DI5 Digital input yellow Input is ON Input is OFF
DO0...DO5 Digital output yellow Output is ON Output is OFF
AI0, AI1*) Analog input yellow Input is ON Input is OFF
AO Analog output yellow Output is ON Output is OFF
*) The analog inputs can be configured as digital inputs
1.2.1.3.9 Measuring Ranges
Risk of invalid analog input values!
The analog input values may be invalid if they exceed the measuring range of
the inputs.
Make sure that the analog signal at the connection terminals is always within
the signal range.
Range 0 V...10 V Digital value
Decimal Hex.
Overflow > 11.7589 32767 7FFF
Measured value too
high
11.7589
:
10.0004
32511
:
27649
7EFF
:
6C01
Normal range 10.0000
:
0.0004
27648
:
1
6C00
:
0001
0.0000 0 0000
The represented resolution corresponds to 10 bits.
1.2.1.3.10 Output Ranges
Range 0 V...+10 V 0 mA...20 mA Digital value
Decimal Hex.
Overflow 11.75
11.75
23.50
23.50
32767
:
32512
7FFF
:
7F03
Output value too
high
11.75
:
10.01
23.50
:
20.02
32480
:
27680
7EE0
:
6C20
Normal range 10.00
:
0.01
20.00
:
0.02
27648
:
32
6C00
:
20
Device Specifications
Processor Modules > AC500-eCo
2019/04/17 3ADR010121, 13, en_US 59