State LEDs
LED State Color LED = OFF LED = ON
Inputs I0...I7 Digital input Yellow Input is OFF Input is ON
Outputs
NO0...NO7
Digital output Yellow Output is
OFF
Output is ON
Technical Data
The System Data of AC500-eCo apply
Ä
Chapter 2.5.1 “System Data AC500-eCo”
on page 1192
Only additional details are therefore documented below.
Parameter Value
Process supply voltage L+
Connections Terminal 20 for L+ (+24 VDC). The
minus pole is provided by the I/O-Bus.
Rated value 24 VDC
Current consumption via L+ 50 mA
Inrush current (at power-up) 0.0035 A²s
Max. ripple 5 %
Protection against reversed voltage Yes
Rated protection fuse for L+ Recommended; the outputs must be pro-
tected by a 3 A fast fuse
Current consumption from 24 VDC power supply at
the L+/UP and M/ZP terminals of the CPU/bus
module
Ca. 5 mA
Galvanic isolation Yes, between the input group and the
output group and the rest of the module
Isolated groups 3 groups (1 group for 8 input channels, 2
groups for 8 output channels)
Surge-voltage (max.) 35 VDC for 0.5 s
Max. power dissipation within the module 2.3 W
Weight Ca. 150 g
Mounting position Horizontal or vertical
Cooling The natural convection cooling must not
be hindered by cable ducts or other parts
in the switch-gear cabinet.
No effects of multiple overloads on isolated multi-channel modules occur, as every channel is
protected individually by an external fuse.
No effects of
multiple over-
loads
I/O Modules > Digital I/O Modules
2019/04/173ADR010121, 13, en_US294