EasyManua.ls Logo

ABB AC500 PLC - State LEDs; Technical Data

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
State LEDs
LED State Color LED = OFF LED = ON
Inputs I0...I7 Digital input Yellow Input is OFF Input is ON
Outputs
NO0...NO7
Digital output Yellow Output is
OFF
Output is ON
Technical Data
The System Data of AC500-eCo apply
Ä
Chapter 2.5.1 “System Data AC500-eCo”
on page 1192
Only additional details are therefore documented below.
Parameter Value
Process supply voltage L+
Connections Terminal 20 for L+ (+24 VDC). The
minus pole is provided by the I/O-Bus.
Rated value 24 VDC
Current consumption via L+ 50 mA
Inrush current (at power-up) 0.0035 A²s
Max. ripple 5 %
Protection against reversed voltage Yes
Rated protection fuse for L+ Recommended; the outputs must be pro-
tected by a 3 A fast fuse
Current consumption from 24 VDC power supply at
the L+/UP and M/ZP terminals of the CPU/bus
module
Ca. 5 mA
Galvanic isolation Yes, between the input group and the
output group and the rest of the module
Isolated groups 3 groups (1 group for 8 input channels, 2
groups for 8 output channels)
Surge-voltage (max.) 35 VDC for 0.5 s
Max. power dissipation within the module 2.3 W
Weight Ca. 150 g
Mounting position Horizontal or vertical
Cooling The natural convection cooling must not
be hindered by cable ducts or other parts
in the switch-gear cabinet.
No effects of multiple overloads on isolated multi-channel modules occur, as every channel is
protected individually by an external fuse.
No effects of
multiple over-
loads
Device Specifications
I/O Modules > Digital I/O Modules
2019/04/173ADR010121, 13, en_US294

Table of Contents

Related product manuals